A generating station feeds 100 kW into a transmission line at 5000 V. The two wires of the line have a total resistance of 20 ohm. At the far end a step-down transformer of efficiency 95 percent supplies the consumers. The power delivered to the consumers, in kW, is
Answer: (C) 87.4 kW Status: Verified (T1). Checked by code and independent solves on 2026-11-20.
- 92.0 kW
- 87.0 kW
- 87.4 kW
- 80.0 kW
Solution
- Line current I = P/V = 100000/5000 = 20 A.
- Line loss = I² R = 400 x 20 = 8000 W = 8 kW, so 92 kW reaches the transformer.
- Output = 0.95 x 92 = 87.4 kW.
Fast method
Loss is 8 percent in the line; 5 percent of the remaining 92 kW, not of 100 kW, is lost in the transformer. Subtracting 8 and 5 from 100 gives the tempting 87.0 kW.
Expected time: about 150 seconds. Difficulty: hard.
Topic page: AC power, generator and transformer